There are 2 type of wirings. “Power wiring” and “Control wiring“.

For better understanding, Heating element controlled by temperature controller is shown below.

In this arrangement, Yellow and black colored wiring represents the power wiring. Power wiring’s rated voltage is 230V AC. In power wiring, Heater load current flows while it is also act as a power source for temperature controller.

While Blue and red colored wiring represents the control wiring. Where controller command the control power to SSR further SSR control the power to heater. Controller produces the rated voltage of 12V DC.

Schematic diagram shows Heating element controlled by temperature controller
Schematic diagram shows Heating element controlled by temperature controller

In the arrangement above, Controller produces the command either on or either off. That is simple on off control. But in control valve control systems, Valve needs to be regulate from 0% to 100%. These type of control are done by 4-20mA signals. In this post, Next we are going to discuss 4-20mA signals.

What is a 4-20 mA signal ?

“4-20mA is “current loop signal“. This signal ranges from 4mA to 20mA. This 4-20mA signal can be used as an input or can be used as an output. Since it is a type of range, It is more than just on and off. It is like controlling the system from 0 to 100%.

PID controllers and process controllers have provision of 4 to 20 mA signal. According to the set parameters and set target, These controllers by regulating the 4 to 20mA signal, try to achieve the set target.

An image of PID controller P104 is shown below. This PID controller produces mA signal output to control the pneumatic actuator valve. Further this valve control the steam flow or chilled water flow to achieve the target value.

Running PID controller P104 by Eurotherm
PID controller P104 by Eurotherm

For better understanding, We are taking an examples of “Process controller” and “Normal temperature controller“.

In normal temperature controllers, There are two scenario either it will completely open the valve or it will completely close the valve. A margin need to be adjust around the set value in normal temperature controllers. Normal controllers do not have precise control as it fluctuate around the set value.

In a Process controller, PID is actually controlling the control valve in a proportion of percentage from 0% to 100%. PID produces the milli amps output from 4 to 20mA. At 4mA, valve get 0% open While at 20mA, valve will get 100% opened

Wiring 4-20mA devices

These devices comes in 2 wires, 3 wires and 4 wires.

Collage images of temperature sensor IFM TA2232
Terminals connections of temperature sensor IFM TA2232

Use of 4-20mA signal !

4 to 20mA signals are generated by electronic circuitry according to the “stored instructions” & “present input signals”. It is either used to control the “electromagnetic field of inductive coil” or as a feedback to another “digital circuitry“.

4 to 20mA signal for Inductive coils

In this, Signal current produced by the device, flows through the coil. According to the current level, Electromagnetic coil produces the magnetic field.

An primary power source such as compressed air at rated air pressure is already connected to the system while this signal current actually controls the air pressure going to the actuator valve.

This closed loop signal try to control the air pressure input at positioner valve. So that valve opening can get controlled from 0 to 100%.

An image of pneumatic positioner valve is shown below :

Pneumatic positioner valve
Pneumatic positioner valve

4 to 20mA signal as a feedback to digital circuitry

In this arrangement, 4-20mA device or instrument feed the 4 to 20mA signal to another digital device. The receiver device further reads the signal according to the stored instructions and produces the output or reflects the correspond reading. This process act like a “feedback“.

An image of flush pressure sensor with display is shown below. Sensor produces the 4 to 20mA output signal.

Flush pressure sensor with display |  PI1703 by Ifm
Flush pressure sensor with display | PI1703 by Ifm

An image of TA2232 Temperature transmitter by IFM is shown below. Sensor produces the 4 to 20mA output signal.

Collage images of TA2232 Temperature transmitter by IFM
TA2232 Temperature transmitter by IFM

Why 4 mA and Not 0 mA?

This concept is called “Live Zero.” 0 mA can not be taken as initial value Which can be an error in case of broken wire, power failure and sensor failure.

Advantage of 4-20mA signal

The key advantage is that current remains the same throughout a series circuit, regardless of cable resistance. Apart it offers :

Common Applications

Common Problems and Troubleshooting

Know the process value (Signal current)

If we are working in the field of instrumentation, It is very important to know about the proportion of process value and signal value. For 4 to 20mA range, there is formula :

i=(PV-Minimum value)/(Maximum value-Minimum value)*16+4

Where,

At 120°C, Signal current will be 13.6mA.

Frequently Asked Questions (FAQs) About 4–20 mA Signals

1. What is a 4–20 mA signal?

A 4–20 mA signal is an analog current loop standard widely used in industrial automation to transmit process variables such as pressure, temperature, level, and flow over long distances.

2. Why does the signal start at 4 mA instead of 0 mA?

The 4 mA value represents the “live zero.” It allows the receiving device to distinguish between a valid zero measurement (4 mA) and a fault condition such as a broken wire (0 mA).

3. What does 4 mA represent?

Typically, 4 mA corresponds to the minimum value of the measured process variable (0%, lower range value).

4. What does 20 mA represent?

20 mA represents the maximum value of the measured process variable (100%, upper range value).

5. Why is 4–20 mA preferred over voltage signals?

Current signals are less affected by voltage drops, electrical noise, and cable resistance, making them more reliable for long-distance transmission.

6. How far can a 4–20 mA signal travel?

Depending on the power supply voltage, cable resistance, and loop load, a 4–20 mA signal can typically travel hundreds or even thousands of meters without significant accuracy loss.

7. How do I convert a 4–20 mA signal into engineering units?

Use the formula:

Process Value=(I4)16×Span+LRV\text{Process Value}=\frac{(I-4)}{16}\times\text{Span}+\text{LRV}Process Value=16(I−4)​×Span+LRV

Where:

8. What happens if the current drops below 4 mA?

A current below 4 mA usually indicates a fault condition, such as sensor failure, wiring problems, or transmitter diagnostics.

9. Can multiple devices be connected in a 4–20 mA loop?

Yes, provided the total loop resistance remains within the transmitter’s load capability and the supply voltage is sufficient.

10. What is a two-wire transmitter?

A two-wire transmitter uses the same pair of wires for both power and signal transmission. It draws operating power directly from the 4–20 mA current loop.

11. What is loop resistance in a 4–20 mA circuit?

Loop resistance is the total resistance of cables, indicators, PLC input cards, barriers, and other devices connected in the current loop.

12. How can I measure a 4–20 mA signal with a multimeter?

The multimeter must be placed in series with the loop and set to the DC current measurement range.

13. Can a PLC directly read a 4–20 mA signal?

Yes. Most PLC analog input modules are designed to accept 4–20 mA signals directly.

14. What process instruments commonly use 4–20 mA signals?

Examples include:

15. Why is 20 mA chosen as the upper limit?

20 mA provides sufficient signal range for accurate measurement while keeping power consumption low and ensuring safe operation in industrial environments.


Leave a Reply

Discover more from BIJLIWALA

Subscribe now to keep reading and get access to the full archive.

Continue reading