MCB tripping again and again? Or not tripping at all?
Before replacing it, you should test whether the MCB is actually faulty.

MCB is a type of protection device. MCB is used to be connected at the back end; before the electrical load. MCB stands for “Miniature circuit breaker“. MCB is a type of “switch cum circuit breaker“. MCB provides protection form “overload “& “short circuit” conditions.

In fault conditions, When fault current crosses the particular current level under certain time limit, It disconnect(trips) the circuit.

2 pole MCB C6 by SIEMENS
2 pole MCB C6 by SIEMENS

This post further will discuss the MCB specifications, Its working & method of testing.

Table of content :

Mcb functions

MCB can be used in a multiple ways such as :

Working mechanism of Mcb

MCB has 2 terminals; Input & output. As name suggest, Input power is connected across input terminal.

When MCB operator get lifted up, Input terminal get connected to output terminal. Potential get available to output terminal. While when MCB operator get lifted down or get trip, Input terminal get disconnected from output terminal.

Image of MCBs. left side connected Mcb, Right side disconnected Mcb
left side connected Mcb, Right side disconnected Mcb

MCB provides protection from “overload “& “short circuit” conditions. “Overload “is slow process phenomenon While “short circuit” is rapid phenomenon. For both the phenomenon, MCB has 2 different working mechanisms :

Inside the MCB , When current exceeds the limit through a Bi-metallic thermal strip, strip get heated up. Due to the heating, Bi-metallic thermal strip produces the bending movement. The bending movement further produces a trigger to trip circuit.

In short circuit situation current exceeds the limit rapidly. This sudden excess current produces an sharp Electro-magnetic field which is used to trigger the trip circuit.

Both the trip mechanism are shown in an image below. Both the mechanism, Whether it is Thermal bimetallic or Electromagnetic coil, triggers the same trip circuit. Some times in some faults, Both the mechanism work together.

A bisect image which shows the internal arrangement inside the MCB
MCB’s internal circuitry elaborated through marking & Indication !

Mcb specifications

The choice of MCB depend upon multiple criterion’s. Some of the most important criterion’s discussed below:

An image of C 32 2 pole MCB is shown below. Different sections of the MCB are marked Which explained next :

1. Terminal Blocks
2. MCB details like Make, Type, Tripping Curve, Current Rating & Voltage Rating
3. Switching Capacity
4. Switching Symbol
5. Operator for manual actuation

An image of 2 pole 32 Amps MCB on which different sections been marked
Image of MCB 2 pole 32 Amps Different specifications marked on MCB

Method of testing of Mcb

There are two situation of MCB testing. Such as :

  1. Testing on de-energized MCB
  2. Testing on energized MCB

Testing on de-energized Mcb

1. Continuity Testing through Multi-meter

In this method, Continuity option available on multi-meter is utilized to test the working of MCB .

Continuity testing of MCB through multimeter
Continuity testing of MCB through multimeter | Continuity shown across connected MCB
Continuity testing of MCB through multimeter
Continuity testing of MCB through multimeter | No continuity shown across disconnected MCB

2. Continuity testing through series test method

In series test method, Potential difference & a bulb are utilized to test the MCB . In Series test method phase/voltage directly passes through the bulb. While neutral or negative is directly connected to one of the terminal of the test specimen.

When these 2 test terminals of series test method are connected with each other, Bulb starts glowing. Bulb only glows when circuit is continuous otherwise bulb do not glows.

A Circuit diagram for series test lamp method
A series circuit shows Series TEST Lamp with 100 Watt Incandescent Bulb

Testing on energized MCB

Safe points to consider before testing the energized MCB :

To test the energized MCB , Multi-meter is utilized to detect the potential difference present across the terminals of MCB . Further there are 2 methods to test the energized MCB .

  1. Potential drop across MCB
  2. Potential at output terminal of MCB

1. Potential drop across MCB

In this method, Potential difference is been checked across both the terminals.

MCB testing drop voltage method
Left side MCB placed in trip position which results potential drop appear MCB . Right side; MCB is placed in connected position which results 0 potential difference appear across the MCB .

2. Potential at output terminal

Potential/Voltage is been checked across the output terminal of MCB . Voltage is been checked with respect to “neutral “or “Earthing“.

  1. When MCB is connected, Voltage on output terminal is equal to voltage at input terminal.
  2. When MCB is disconnected, No voltage appear across output terminal.

If Both the above said conditions are true than MCB is working fine. Otherwise, MCB is faulty.

FAQs for selection of MCB

1. Can I test an MCB without removing it?

Yes, but ensure power is OFF for safety.


2. What is the normal resistance of an Mcb ?

It should be very low (close to 0 ohms).


3. Why does my Mcb trip again and again?

Possible reasons:


4. Is it safe to test Mcb with power ON?

Only for voltage testing and only if you are experienced.


5. Can a multimeter detect a faulty Mcb completely?

It helps identify basic faults, but not all internal issues.


🧾 Conclusion

Testing an MCB using a multi-meter is a simple yet essential skill for maintaining electrical safety. By performing continuity, resistance, and voltage tests, you can quickly determine whether your MCB is functioning properly or needs replacement.

Always follow proper safety precautions and avoid working with live circuits unless you are confident in your skills.

Leave a Reply

Discover more from BIJLIWALA

Subscribe now to keep reading and get access to the full archive.

Continue reading