SELEC TIMER 800XC

This timer operates as continuous alternate cycle with selectable on & off time. Timer’s relay get on & off according to the set time. Both on & off functions have independent time setting which is briefly explained below:

CYCLIC TIMER 800X with unequal on & off time by SELEC
CYCLIC TIMER 800XC with unequal on & off time by SELEC–1

 

SELEC Timer 800x--2
SELEC Timer 800x–2
As shown in an image above, T1 represents off time & T2 represents on time.
We can set whether make the relay ‘ON’ first Or ‘OFF’ first.
When Timer get supply, it makes the relay off up to T1 time after that relay get on for time T2. when T2 time ends, relay again get off up to T1. The timer operates continuously until the power supply goes off.
When timer’s get supply, it makes the relay on for time T2 after that relay get off for time T1. & Then again relay get on for time T2. The timer operates continuously until the power supply goes off.

SPDT Relay

Schematic diagram of SPDT (single pole double through)
Schematic diagram of SPDT (single pole double through)

FEATURES OF SELEC 800X

SPECIFICATIONS OF SELEC 800X

1. Supply Voltage
2. Delay modes
  Cyclic on first or off first
3. Time Ranges
4. Output Contacts
  5A @ 230V AC /24V DC (resistive)
  2C/O SPDT
5. Accuracy
  Setting +-5% of full scale
  Repeat +- 0.5% or 50 msec
6. LED indication
  1.   Power ON
  2.   Relay ON
7. Reset
  On power Interruption
  Reset time<100msec
8. Relay Rating
  5A@230VAC/24VDC (Resistive)
9. Mechanical Endurance
  1*10^7 operations
10. Electrical Endurance
  5*10^4 operations (8A 250VAC)
11. Mounting
  Din rail
12. Size(in mm)
  22.5(W)*76.85(H)*100.5(D)
13. Temperature
14. Humidity
  95% RH
15. Wire size(mm2)
  1.5
16. Tightening torque(N-m)
  0.5
17. Weight
  110 grams
 

TERMINAL CONNECTIONS OF SELEC 800X

Terminals A1&A2 are Timer’s power supply terminals which works on both AC as well as DC supply.(VAC[20 to 240](50/60Hz) & VDC[12 to 240]).
It has two changeover relays(SPDT).
  1. Relay 1[15(common),16(NC) & 18(NO)]
  2. Relay 2[25(common),26(NC) & 28(NO)]
To increase the internal life of the relay of the timer use of snubber circuit is must. For load current less than 0.5amps; connect the load directly to the relay with snubber circuit across it. For load current more than 0.5amps; connect load through contactor & snubber circuit must be connected across the contactor’s coil.

SWITH SETTING OF SELEC 800x

For both the ON & OFF time setting, two variable knobs T1 & T2 are provided whose range from 0 to 10 selectable. For time unit selection whether to set the time unit on second, minute & hour, switch setting is provided on the top As shown in an image–3 below:

Switch settings| timer800X by SELEC
Switch settings| timer800X by SELEC–3

 

There are total 8 switches are provided. Switches in down position are in on position & switches in up position are in off position. In an image3- 1,2,4,6,7 switches are in off position & 3,5,8 switches are in on position.
OFF TIME UNITS– When both the switches 1&2 are in off position than time unit will be second, When 1 is on & 2 in off position than time unit will be minute, When 1 is off & 2 is on than time unit will be hour. Similar the case with ON time which is adjustable with 6&7 switches.
In an image–3, 
1,2 & 6,7 are in off position than it means that both the OFF & ON time are in second. 
3&8 are in On position that means multiplier is 1. Both the times T1 & T2 are adjusted through variable knob at 5 that means for both the times 5*1=5secs is selected. if 3&8 are in Of position than it means that multiplier is 10. Both the times will become 5*10=50Sec.
4&5– 4 is off & 5 is on that means ON time will execute first.
 

APPLICATIONS

Circuit for non continuous conveyor system with SELEC 800X

We can use the timer SELEC 800X at a system where conveyor is taking rest in fixed running intervals. We can say, conveyor has both on & off Time which is selectable. Let suppose conveyor motor is 1.5KW, 3phase 415Volts-50Hz.

In power wiring, 3phase supply directly connected on the contactor through 10Amps 3pole MCB & motor terminals are connected to the contactor through thermal overload relay with ampere range 2.5to 4Amps. Control wiring is explained below:

Circuit for conveyor system with 'SELEC800X'
Circuit for conveyor system with ‘SELEC800X’

In this circuit, we have arranged both the running modes ‘auto & manual’. Mode is selectable through selector switch. In manual mode, Conveyor will run continuously. In auto mode, conveyor will run in ON&OFF intervals through the cyclic timer in which we can set ON&OFF time of conveyor. It doesn’t matter Whether we are running the conveyor in auto or manual mode, we have to start & stop the conveyor through push buttons.

Since all the components have supply voltage is 230V AC that’s why neutral is directly connected to 8 pin relay, Timer & contactor. First, Phase is passing through the NC (Emergency switch) which is used as a safety, Than this phase is passing through the NC (stop) & NO (start) of push button in a series manner. At last, phase is connected to relay coil.

When we press NO(Start) push button, relay’s coil get energized which results relay’s contacts get changed. After that when we release start push button, relay get hold because relay’s NO contacts are connected in parallel across NO (Start).

Another NO of relay is connected to 2way selector switch. Since another NO of relay is connected to phase, after relay get hold phase become available to main contact of selector switch. One point of selector is connected to energize the timer & another point of selector is directly connected with motor’s contactor through NC contact of thermal overload relay. Contactor through NC of thermal overload relay is also connected with timer’s NO.

 

❓ Frequently Asked Questions (FAQs)

1. What is the SELEC 800XC Cyclic Timer?
The SELEC 800XC is a cyclic timer device used in control systems to automatically switch its output on and off in continuous cycles, with independently adjustable on and off durations.

2. How does the cyclic timer work?
It alternates the relay between ON and OFF states based on the set timings: one knob sets the ON duration and another sets the OFF duration. You can also choose whether the cycle starts with ON or OFF.

3. What applications is this timer used for?
This timer is commonly used in automation and industrial control—for example, controlling conveyor systems that need to run periodically with fixed rest intervals.

4. What voltage range does the 800XC support?
It supports a wide supply voltage range from 20 V to 240 V AC and 12 V to 240 V DC, making it suitable for various power systems.

5. What are the key features of this timer?
Key features include:

6. How many relay outputs does the timer have?
The 800XC includes two changeover (SPDT) relay contacts, allowing flexible control of external loads.

7. Can I adjust the time ranges?
Yes — the timer offers multiple time ranges from fractions of a second up to hours for both ON and OFF durations, allowing fine-tuned control.

8. How accurate is the timing?
The timing accuracy is typically within ±5% of full scale, with repeatability around ±0.5% or 50 ms.

9. How is the timer mounted?
It is designed for DIN rail mounting, making it easy to integrate into industrial control panels.

10. What protections or indications does the timer have?
It has LED indicators to show when the power is on and when the relay is active, ensuring easy status monitoring.


Hope, you like the post if you have any doubt, suggestion or query please do comments !

 